The disadvantage of using insulated wires for laying electrical lines in explosion-hazardous places is that sparks are generated due to leakage, which can lead to explosions.
There are three main requirements for laying electrical circuits in explosion-hazardous locations:
1. Electrical circuits in explosion-risk locations mainly include steel pipes and cable wiring. Steel pipe wiring projects must be laid out in the open, and galvanized steel pipes should be used. Cable distribution area 1 should use copper core armored cables; area 2 should also use copper core armored cables. When aluminum core cables are used, reliable copper-aluminum transition joints and other measures should be taken to connect them to electrical equipment.
2. In steel pipe wiring projects, threaded connections should be used between two sections of steel pipes, between steel pipes and their accessories, and between steel pipes and electrical equipment introduction devices, and the number of effective engagement buckles shall not be less than 6; steel pipes and electrical equipment are directly connected Flexible connecting pipes should be installed in places where connections are difficult, and where pipelines pass through expansion joints and settlement joints in buildings.
3. In explosion-risk locations, cables for different purposes should be laid separately, and power and lighting lines must be separated and joint use is strictly prohibited; cables and steel pipe wiring should not be laid in pipe trenches and ventilation trenches; buried armored cables are not allowed to have intermediate joints or Buried junction box; explosion-proof motors and fans should give priority to cable entry.
Feb 06, 2024
Are the insulated wires exposed and laid correctly?
Send Inquiry